2-CORE XLPE,SWA,HFFR SHEATHED CABLES AS PER QCS 2014

Products

2C X 1.5 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22002SXZHSH30BS0

  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 209 kg/km
  • Nominal outer diameter: 11.2 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

2C X 2.5 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22003SXZHSH30BS0

  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 270 kg/km
  • Nominal outer diameter: 12.6 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

2C X 4 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22004SXZHSH30BS0

  • Conductor cross-section: 4 mm²
  • Approximate weight: 334 kg/km
  • Nominal outer diameter: 13.7 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 39 A
  • Voltage drop, 3 conductors: 8.7 V/A.km

 

2C X 6 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22006SXZHSH30BS0

  • Conductor cross-section: 6 mm²
  • Approximate weight: 392 kg/km
  • Nominal outer diameter: 14.8 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 49 A
  • Voltage drop, 3 conductors: 5.9 V/A.km

 

2C X 10 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22010SXZHSH30BS0

  • Conductor cross-section: 10 mm²
  • Approximate weight: 522 kg/km
  • Nominal outer diameter: 16.4 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 78 A
  • Permissible current rating when buried: 65 A
  • Voltage drop, 3 conductors: 3.5 V/A.km

 

2C X 16 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22016SXZHSH30BS0

  • Conductor cross-section: 16 mm²
  • Approximate weight: 767 kg/km
  • Nominal outer diameter: 18.9 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 84 A
  • Voltage drop, 3 conductors: 2.2 V/A.km

 

2C X 25 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22025SXZHSH30BS0

  • Conductor cross-section: 25 mm²
  • Approximate weight: 1056 kg/km
  • Nominal outer diameter: 22.4 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 131 A
  • Permissible current rating when buried: 107 A
  • Voltage drop, 3 conductors: 1.7 V/A.km

 

2C X 35 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22035SXZHSH30BS0

  • Conductor cross-section: 35 mm²
  • Approximate weight: 1466 kg/km
  • Nominal outer diameter: 25.5 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 162 A
  • Permissible current rating when buried: 129 A
  • Voltage drop, 3 conductors: 1.2 V/A.km

 

2C X 50 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22050SXZHSH30BS0

  • Conductor cross-section: 50 mm²
  • Approximate weight: 1823 kg/km
  • Nominal outer diameter: 28.6 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 153 A
  • Voltage drop, 3 conductors: 0.89 V/A.km

 

2C X 70 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22070SXZHSH30BS0

  • Conductor cross-section: 70 mm²
  • Approximate weight: 2688 kg/km
  • Nominal outer diameter: 33.5 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 251 A
  • Permissible current rating when buried: 188 A
  • Voltage drop, 3 conductors: 0.6 V/A.km

 

2C X 95 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22095SXZHSH30BS0

  • Conductor cross-section: 95 mm²
  • Approximate weight: 3282 kg/km
  • Nominal outer diameter: 37.1 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 304 A
  • Permissible current rating when buried: 226 A
  • Voltage drop, 3 conductors: 0.45 V/A.km

 

2C X 120 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22120SXZHSH30BS0

  • Conductor cross-section: 120 mm²
  • Approximate weight: 3885 kg/km
  • Nominal outer diameter: 40.5 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 353 A
  • Permissible current rating when buried: 257 A
  • Voltage drop, 3 conductors: 0.37 V/A.km

 

2C X 150 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22150SXZHSH30BS0

  • Conductor cross-section: 150 mm²
  • Approximate weight: 4761 kg/km
  • Nominal outer diameter: 44.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 406 A
  • Permissible current rating when buried: 287 A
  • Voltage drop, 3 conductors: 0.3 V/A.km

 

2C X 185 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22185SXZHSH30BS0

  • Conductor cross-section: 185 mm²
  • Approximate weight: 5952 kg/km
  • Nominal outer diameter: 49.7 mm
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Permissible current rating in open air: 463 A
  • Permissible current rating when buried: 324 A
  • Voltage drop, 3 conductors: 0.26 V/A.km

 

2C X 240 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22240SXZHSH30BS0

  • Conductor cross-section: 240 mm²
  • Approximate weight: 7466 kg/km
  • Nominal outer diameter: 54.3 mm
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Permissible current rating in open air: 546 A
  • Permissible current rating when buried: 375 A
  • Voltage drop, 3 conductors: 0.21 V/A.km

 

2C X 300 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22300SXZHSH30BS0

  • Conductor cross-section: 300 mm²
  • Approximate weight: 8729 kg/km
  • Nominal outer diameter: 59.5 mm
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
  • Permissible current rating in open air: 628 A
  • Permissible current rating when buried: 419 A
  • Voltage drop, 3 conductors: 0.18 V/A.km

 

2C X 400 Sq.mm CU/XLPE/SWA/HFFR NEW

Nexans ref. 22400SXZHSH30BS0

  • Conductor cross-section: 400 mm²
  • Approximate weight: 10822 kg/km
  • Nominal outer diameter: 67.6 mm
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating in open air: 731 A
  • Permissible current rating when buried: 439 A
  • Voltage drop, 3 conductors: 0.17 V/A.km

 

Description

Description

Standards

  • Product
    BS 6724
  • Test
    IEC 60332-3-24 Cat.C

Scope

 This specification covers two core, XLPE insulated cables for use on the Qatar Power Systems ,Street lightning and Small wiring systems. These cables are complying with BS 6724 and QCS 2014 Standards .

 

Design

 

1. Conductor

Plain annealed high-conductivity Stranded Copper Class 2 conforming to BS EN 60228

 

2. Insulation

XLPE insulation Type GP8 conforming to BS 7655-1

 

3. Filling or Bedding

 Extruded HFFR

 

4. Armour

Single layer of Galvanised Steel Wires (GSWA)

 

5. Outer Sheath

Halogen Free Flame Retardant (HFFR)

 - Flame retardant : IEC60332-3-24 CAT C

 - Colour :  Black

 

Marking

NO.OF CORES X Sq.mm CU/XLPE/SWA/HFFR 600/1000 V  BS 6724 MADE IN QATAR QICC-NEXANS Years  Meters

 

 

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Circular
Core identification
Red,Black
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
2

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
12 (xD)
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. pulling force during laying
50 N/mm2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close