1-CORE CU,XLPE,AWA,PVC SHEATHED CABLES FOR OIL & GAS PROJECTS

Products

1C X 35 Sq.mm NEW

Nexans ref. 21035QXZVABZ1BE0

  • Conductor cross-section: 35 mm²
  • Approximate weight: 559 kg/km
  • Nominal outer diameter: 17.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 176 A
  • Permissible current rating when buried: 129 A

 

1C X 50 Sq.mm NEW

Nexans ref. 21050QXZVABZ1BE0

  • Conductor cross-section: 50 mm²
  • Approximate weight: 707 kg/km
  • Nominal outer diameter: 18.4 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 216 A
  • Permissible current rating when buried: 153 A

 

1C X 70 Sq.mm NEW

Nexans ref. 21070QXZVABZ1BE0

  • Conductor cross-section: 70 mm²
  • Approximate weight: 943 kg/km
  • Nominal outer diameter: 20.4 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 279 A
  • Permissible current rating when buried: 188 A

 

1C X 95 Sq.mm NEW

Nexans ref. 21095QXZVABZ1BE0

  • Conductor cross-section: 95 mm²
  • Approximate weight: 1220 kg/km
  • Nominal outer diameter: 22.1 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 342 A
  • Permissible current rating when buried: 226 A

 

1C X 120 Sq.mm NEW

Nexans ref. 21120QXZVABZ1BE0

  • Conductor cross-section: 120 mm²
  • Approximate weight: 1477 kg/km
  • Nominal outer diameter: 23.9 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 400 A
  • Permissible current rating when buried: 257 A

 

1C X 150 Sq.mm NEW

Nexans ref. 21150QXZVABZ1BE0

  • Conductor cross-section: 150 mm²
  • Approximate weight: 1772 kg/km
  • Nominal outer diameter: 25.6 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 464 A
  • Permissible current rating when buried: 287 A

 

1C X 185 Sq.mm NEW

Nexans ref. 21185QXZVABZ1BE0

  • Conductor cross-section: 185 mm²
  • Approximate weight: 2177 kg/km
  • Nominal outer diameter: 28.2 mm
  • Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
  • Permissible current rating in open air: 533 A
  • Permissible current rating when buried: 324 A

 

1C X 240 Sq.mm NEW

Nexans ref. 21240QXZVABZ1BE0

  • Conductor cross-section: 240 mm²
  • Approximate weight: 2737 kg/km
  • Nominal outer diameter: 30.5 mm
  • Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
  • Permissible current rating in open air: 634 A
  • Permissible current rating when buried: 375 A

 

1C X 300 Sq.mm NEW

Nexans ref. 21300QXZVABZ1BE0

  • Conductor cross-section: 300 mm²
  • Approximate weight: 3348 kg/km
  • Nominal outer diameter: 33.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
  • Permissible current rating in open air: 736 A
  • Permissible current rating when buried: 419 A

 

1C X400 Sq.mm NEW

Nexans ref. 21400QXZVABZ1BE0

  • Conductor cross-section: 400 mm²
  • Approximate weight: 4248 kg/km
  • Nominal outer diameter: 37.2 mm
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating in open air: 868 A
  • Permissible current rating when buried: 717 A

 

1C X 500 Sq.mm NEW

Nexans ref. 21500QXZVABZ1BE0

  • Conductor cross-section: 500 mm²
  • Approximate weight: 5375 kg/km
  • Nominal outer diameter: 40.9 mm
  • Max. DC resistance of the conductor at 20°C: 0.036 Ohm/km
  • Permissible current rating in open air: 998 A
  • Permissible current rating when buried: 791 A

 

1C X630 Sq.mm NEW

Nexans ref. 21630QXZVABZ1BE0

  • Conductor cross-section: 630 mm²
  • Approximate weight: 6771 kg/km
  • Nominal outer diameter: 45.2 mm
  • Max. DC resistance of the conductor at 20°C: 0.028 Ohm/km
  • Permissible current rating in open air: 1151 A
  • Permissible current rating when buried: 861 A

 

Description

Description

Standards

  • International
    IEC 60332-3-22 Cat.A; IEC 60502-1

Scope

The Cables covered in this specification are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plants...). 

 

Design

 

1. Conductor

Plain annealed high-conductivity Stranded Copper Class 2 conforming to BS EN 60228

 

2. Insulation

XLPE

 

3. Filling or Bedding

 Extruded PVC

 

4. Armour

Single layer of Aluminium Round Wires (AWA)

 

5. Outer Sheath

Flame Retardant PVC

 - Flame retardant : IEC60332-3-22 CAT A

 - Colour :  Black

 

Marking (by Embossing/Engraving)

NO.OF CORES X Sq.mm CU/XLPE/AWA/PVC FR 600/1000 V  IEC 60502-1 IEC 60332-3-22 MADE IN QATAR QICC-NEXANS Years  Meters

 

 

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Stranded class 2
Conductor shape
Circular
Insulation
XLPE
Inner sheath
PVC
Armour type
Aluminium Wire
Outer sheath
Flame retardant PVC
Colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Thermal soil resistivity dry zone
2.5 °K.m/W

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
15 (xD)
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Laying depth, center of system
700 mm
Max. pulling force during laying
50 N/mm2
Resistant to termites
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close