11kV Multicore MV Cables (KAHRAMAA)

Products

3x70

Nexans ref. 23070EXCVSR09EA3

  • Conductor cross-section: 70 mm²
  • Nominal outer diameter: 57.5 mm
  • Approximate weight: 7250 kg/km
  • Permissible current rating in open air: 220 A
  • Permissible current rating when buried: 157 A
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km

 

3x120

Nexans ref. 23120EXCVSR09EA3

  • Conductor cross-section: 120 mm²
  • Nominal outer diameter: 66.3 mm
  • Approximate weight: 10365 kg/km
  • Permissible current rating in open air: 306 A
  • Permissible current rating when buried: 229 A
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km

 

3x185

Nexans ref. 23185EXCVSR09EA3

  • Conductor cross-section: 185 mm²
  • Nominal outer diameter: 70.5 mm
  • Approximate weight: 12000 kg/km
  • Permissible current rating in open air: 394 A
  • Permissible current rating when buried: 267 A
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km

 

3x240

Nexans ref. 23240EXCVSR09EA3

  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 77.4 mm
  • Approximate weight: 15100 kg/km
  • Permissible current rating in open air: 460 A
  • Permissible current rating when buried: 308 A
  • Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km

 

3x300

Nexans ref. 23300EXCVSR09EA3

  • Conductor cross-section: 300 mm²
  • Nominal outer diameter: 82.2 mm
  • Approximate weight: 17450 kg/km
  • Permissible current rating in open air: 518 A
  • Permissible current rating when buried: 344 A
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km

 

Description

Description

Standards

  • International
    IEC 60332-1; IEC 60502-2

Scope

 This specification covers multi-core, XLPE insulated cables for use on the Qatar 11kV Distribution System for underground installation in general and rarely to be used for above ground.  These cables are complying with IEC 60502-2 and Kahramaa Standard specification No.EP-MS-P4/S3-030

 

Design

1. Conductor

Plain annealed high-conductivity Stranded Copper Class 2 conforming to IEC 60228.

2. Insulation

Extruded Inner semiconductive layer,XLPE insulation and extruded outer semiconductive layer.

3. Metalic Screen

Copper wire screen with open helix copper tape each layer.

4. Inner Sheathing or Bedding

Extruded PVC 

5. Armour

Galvanized Steel Wire Armour (SWA) with Non-conducting Water Blocking Tape above and below the armour layer

6. Outer Sheath

Polyvinyl Chloride 'PVC'

 - Flame retardant : IEC60332-1

 - Colour :  Red

 

Marking

KAHRAMAA 11000V XLPE NO.OF CORES X Sq.mm IEC 60502-2 MADE IN QATAR QICC-NEXANS Years  Meters

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Stranded class 2
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
Semi-conducting compound
Screen
Copper wire + copper tape
Inner sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC compound
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
3

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
6.35 / 11 kV
Thermal soil resistivity wet zone
2.5 °K.m/W

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient air temperature
45 °C
Ambient ground temperature
35 °C
Laying depth, center of system
1000 mm
Bending factor when laying
30 (xD)
Bending factor when installed
15 (xD)
Flame retardant
IEC 60332-1
Max. pulling force during laying
50 N/mm2

Resources

Resources

Selling & delivery Information


Note: Upon Request ,Cables will be supplied on specific drum lengths
Tolerance on Outerdiameter : +/-7%

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close