3x240

Description

Description

Standards

  • International
    IEC 60332-1; IEC 60502-2

Scope

 This specification covers multi-core, XLPE insulated cables for use on the Qatar 11kV Distribution System for underground installation in general and rarely to be used for above ground.  These cables are complying with IEC 60502-2 and Kahramaa Standard specification No.KM-EPM-D-CBL-11-XLPE-UGD-1&3-CORE

Design

1. Conductor

Plain annealed high-conductivity Stranded Copper Class 2 conforming to IEC 60228.

2. Insulation

Extruded Inner semiconductive layer,XLPE insulation and extruded outer semiconductive layer.

3. Metalic Screen

Copper wire screen with open helix copper tape each layer.

4. Inner Sheathing

Extruded PVC 

5. Armour

Galvanized Steel Wire Armour (SWA) with Non-conducting Water Blocking Tape above and below the armour layer

6. Outer Sheath

Polyvinyl Chloride 'PVC'

 - Flame retardant : IEC60332-1

 - Colour :  Red

 

 

Marking (by Embossing)

KAHRAMAA/ENA 11000V XLPE NO.OF CORES X Sq.mm IEC 60502-2  Years QICC-NEXANS MADE IN QATAR    Meters

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation Conditions:

1. Air Temperature : 50 Deg

2. Ground Temperature: 40 Deg.

3. Soil Thermal Resistivity : 2.0 k.m/W

4. Depth of lay : 0.8 m

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Stranded class 2
Material of the inner semi-conductor
Semi-conducting compound
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
Semi-conducting compound
Core identification
By Identification tapes - Red,Yellow,Blue
Screen
Copper wire + copper tape
Inner sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC compound
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
240 mm²
Nominal outer diameter
79.7 mm
Approximate weight
15000 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
6.35 / 11 kV
Permissible current rating in open air
434 A
Permissible current rating when buried
330 A
Permissible short circuit current
19.9 kA
Permissible short circuit current conductor 1s
34.3 kA
Screen fault current carrying capacity for 1 second
- kA
Thermal soil resistivity wet zone
2 °K.m/W
Max. DC resistance of the conductor at 20°C
0.075 Ohm/km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient air temperature
50 °C
Ambient ground temperature
40 °C
Laying depth, center of system
800 mm
Bending factor when installed
12 (xD)
Flame retardant
IEC 60332-1
Max. pulling force during laying
50 N/mm2

Resources

Resources

Selling & delivery Information


Note: Upon Request ,Cables will be supplied on specific drum lengths
Tolerance on Outerdiameter : +/-7%

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close