2-CORE XLPE,SWA,PVC SHEATHED CABLES AS PER QCS 2014
2-CORE XLPE,SWA,PVC SHEATHED CABLES AS PER QCS 2014
2-CORE XLPE,SWA,PVC SHEATHED CABLES AS PER QCS 2014
Read more2C X 1.5 NEW
Nexans ref. 22002FXZVSB09BS0
- Conductor cross-section: 1.5 mm²
- Approximate weight: 236 kg/km
- Nominal outer diameter: 11.2 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 25 A
- Permissible current rating when buried: 23 A
- Voltage drop, 3 conductors: 22.8 V/A.km
2C X 2.5 NEW
Nexans ref. 22003FXZVSB09BS0
- Conductor cross-section: 2.5 mm²
- Approximate weight: 304 kg/km
- Nominal outer diameter: 12.6 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 33 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
2C X 4 NEW
Nexans ref. 22004FXZVSB09BS0
- Conductor cross-section: 4 mm²
- Approximate weight: 371 kg/km
- Nominal outer diameter: 13.7 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 44 A
- Permissible current rating when buried: 39 A
- Voltage drop, 3 conductors: 8.7 V/A.km
2C X 6 NEW
Nexans ref. 22006FXZVSB09BS0
- Conductor cross-section: 6 mm²
- Approximate weight: 451 kg/km
- Nominal outer diameter: 14.8 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 56 A
- Permissible current rating when buried: 49 A
- Voltage drop, 3 conductors: 5.9 V/A.km
2C X 10 NEW
Nexans ref. 22010FXZVSB09BS0
- Conductor cross-section: 10 mm²
- Approximate weight: 588 kg/km
- Nominal outer diameter: 16.4 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 78 A
- Permissible current rating when buried: 65 A
- Voltage drop, 3 conductors: 3.5 V/A.km
2C X 16 NEW
Nexans ref. 22016FXZVSB09BS0
- Conductor cross-section: 16 mm²
- Approximate weight: 847 kg/km
- Nominal outer diameter: 18.9 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 99 A
- Permissible current rating when buried: 84 A
- Voltage drop, 3 conductors: 2.2 V/A.km
2C X 25 NEW
Nexans ref. 22025FXZVSB09BS0
- Conductor cross-section: 25 mm²
- Approximate weight: 1194 kg/km
- Nominal outer diameter: 22.4 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 131 A
- Permissible current rating when buried: 107 A
- Voltage drop, 3 conductors: 1.7 V/A.km
2C X 35 NEW
Nexans ref. 22035FXZVSB09BS0
- Conductor cross-section: 35 mm²
- Approximate weight: 1627 kg/km
- Nominal outer diameter: 25.6 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 162 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.2 V/A.km
2C X 50 NEW
Nexans ref. 22050FXZ6SB09BS0
- Conductor cross-section: 50 mm²
- Approximate weight: 1829 kg/km
- Nominal outer diameter: 28.3 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 197 A
- Permissible current rating when buried: 153 A
- Voltage drop, 3 conductors: 0.89 V/A.km
2C X 70 NEW
Nexans ref. 22070FXZ6SB09BS0
- Conductor cross-section: 70 mm²
- Approximate weight: 2586 kg/km
- Nominal outer diameter: 33.2 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 251 A
- Permissible current rating when buried: 188 A
- Voltage drop, 3 conductors: 0.6 V/A.km
2C X 95 NEW
Nexans ref. 22095FXZ6SB09BS0
- Conductor cross-section: 95 mm²
- Approximate weight: 3282 kg/km
- Nominal outer diameter: 36.8 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 304 A
- Permissible current rating when buried: 226 A
- Voltage drop, 3 conductors: 0.45 V/A.km
2C X 120 NEW
Nexans ref. 22120FXZ6SB09BS0
- Conductor cross-section: 120 mm²
- Approximate weight: 3965 kg/km
- Nominal outer diameter: 40.2 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 353 A
- Permissible current rating when buried: 257 A
- Voltage drop, 3 conductors: 0.37 V/A.km
2C X 150 NEW
Nexans ref. 22150FXZ6SB09BS0
- Conductor cross-section: 150 mm²
- Approximate weight: 4691 kg/km
- Nominal outer diameter: 43.7 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 406 A
- Permissible current rating when buried: 287 A
- Voltage drop, 3 conductors: 0.3 V/A.km
2C X 185 NEW
Nexans ref. 22185FXZ6SB09BS0
- Conductor cross-section: 185 mm²
- Approximate weight: 6110 kg/km
- Nominal outer diameter: 49.4 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 463 A
- Permissible current rating when buried: 324 A
- Voltage drop, 3 conductors: 0.26 V/A.km
2C X 240 NEW
Nexans ref. 22240FXZ6SB09BS0
- Conductor cross-section: 240 mm²
- Approximate weight: 7379 kg/km
- Nominal outer diameter: 54.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 546 A
- Permissible current rating when buried: 375 A
- Voltage drop, 3 conductors: 0.21 V/A.km
2C X 300 NEW
Nexans ref. 22300FXZ6SB09BS0
- Conductor cross-section: 300 mm²
- Approximate weight: 8885 kg/km
- Nominal outer diameter: 59.2 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 628 A
- Permissible current rating when buried: 419 A
- Voltage drop, 3 conductors: 0.18 V/A.km
Description
Description
Standards
-
InternationalIEC 60332-1
-
NationalBS 5467
Scope
This specification covers two core, XLPE insulated cables for use in Qatar Power Systems ,Street lighting and Small wiring systems. These cables are complying with BS 5467 and QCS 2014 Standards .
Design
1. Conductor
Plain annealed high-conductivity Stranded Copper Class 2 conforming to BS EN 60228
2. Insulation
XLPE insulation Type GP8 conforming to BS 7655-1
3. Filling or Bedding
Extruded PVC
4. Armour
Single layer of Galvanised Steel Wires (GSWA)
5. Outer Sheath
Polyvinyl Chloride 'PVC'
- Flame retardant : IEC60332-1
- Colour : Black
Marking
NO.OF CORES X Sq.mm CU/XLPE/SWA/PVC 600/1000 V BS 5467 MADE IN QATAR QICC-NEXANS Years Meters
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania