Pilot Cable 1kV as per KHARAMMA SPECIFICATION
Description
Description
Standards
-
ProductIEC 60502-1
-
TestIEC 60332-1
Scope
These cables are used on Standard Pilot Wire Protection Schemes and Telecommunication Purposes.
The cable shall be inconformity with IEC 60502-1 and Kahramaa standard specification No. : KM-EPM-D-CBL-LV-XLPE-MULTICORE
Design
1. Conductor
Stranded annealed copper conductor circular in shape in accordance with class 2 of IEC 60228
2. Standard Size
Nominal Size shall be 4C X 4 mm2 + 4 X 2C X 1.5 mm2
3. Insulation
Cross Linked Polyethylene "XLPE"
Core Identification : Red,Yellow,Blue,Black for 4mm2 ; Black & White with White/Black Numbering for 1.5 mm2
4. Inner Sheath or Bedding
Extruded bedding "PVC".
5. Armour
Single layer of Galvanized Steel wires "SWA" with Water blocking tape above and under the armour layer.
6. Outer Sheath
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 60332-1 or equivalent
Extruded bedding "PVC".
5. Armour
Single layer of Galvanized Steel wires "SWA" with Water blocking tape above and under the armour layer.
6. Outer Sheath
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 60332-1 or equivalent
Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 60332-1 or equivalent
Marking :
KAHRAMAA 600/1000V LV XLPE 4 X 4 + 4 X 2 X 1.5 mm² IEC 60502-1 MADE IN QATAR QICC-Nexans Years Meters Air Temperature : 45 Deg. Ground Temperature: 35 Deg. Soil Thermal Resistivity : 2.5 k.m/W Depth of lay : 1.0 m Installation Conditions:
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper class 2
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Insulation
XLPE (Cross-linked Polyethylene)
Inner sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Number of cores
4
Conductor cross-section
4 mm²
Approximate weight
1370 kg/km
Nominal outer diameter
28.5 mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
4.61 Ohm/km
Permissible current rating in open air
36 A
Permissible current rating when buried
34 A
Permissible short circuit current conductor 1s
0.6 kA
Permissible short circuit current screen 1s
3.2 kA
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when installed
7.5 (xD)
Flame retardant
IEC 60332-1