Pilot Cable 1kV as per KHARAMMA SPECIFICATION

Products

4x4mm2 + 4Px1.5mm2 1kV NEW

Nexans ref. 2P004BXZDSB09BA3

  • Packaging: m

 

Description

Description

Standards

  • International
    IEC 60332-1; IEC 60502-1

Scope

 

These cables are used on Standard Pilot Wire Protection Schemes and Telecommunication Purposes.

The cable shall be inconformity with IEC 60502-1  and Kahramaa standard specification No. : KM-EPM-D-CBL-LV-XLPE-MULTICORE

 

 

Design

 

1. Conductor
      Stranded annealed  copper conductor circular in shape in accordance with  class 2 of  IEC 60228

 

2. Standard Size

       Nominal Size shall be 4C X 4 mm2 + 4 X 2C X 1.5 mm2

 

3. Insulation
      Cross Linked Polyethylene "XLPE"
      Core Identification : Red,Yellow,Blue,Black for 4mm2 ; Black & White with White/Black Numbering for 1.5 mm2

4. Inner Sheath or Bedding
     Extruded bedding "PVC". 
 

5. Armour
     Single layer of Galvanized Steel wires "SWA" with Water blocking tape above and under the armour layer.
 

6. Outer Sheath
     Polyvinyl Chloride "PVC" ST2, Flame retardant to IEC 60332-1 or equivalent
 

Marking :

 

KAHRAMAA 600/1000V LV XLPE  4 X 4 + 4 X 2 X 1.5 mm²  IEC 60502-1   MADE IN QATAR QICC-Nexans  Years Meters

 

Installation Conditions:

 

  1. Air Temperature : 45 Deg.

  2. Ground Temperature: 35 Deg.

  3. Soil Thermal Resistivity : 2.5 k.m/W

  4. Depth of lay : 1.0 m

 

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper class 2
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Insulation
XLPE (Cross-linked Polyethylene)
Inner sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
4 mm²
Approximate weight
1370 kg/km
Nominal outer diameter
28.5 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
4.61 Ohm/km
Permissible current rating in open air
36 A
Permissible current rating when buried
34 A
Permissible short circuit current conductor 1s
0.6 kA
Permissible short circuit current screen 1s
3.2 kA

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when installed
7.5 (xD)
Flame retardant
IEC 60332-1

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close